Assessment Year | 2025 |
---|---|
Principal Product | Plastic Pour Bottles |
NAICS | 339112: Surgical and Medical Instrument Manufacturing |
SIC | 5047: Medical, Dental, and Hospital Equipment and Supplies |
Sales Range | $50 M to 100M |
# of Employees | 450 |
Plant Area |
1,000,000
ft2
|
Annual Production | 70,000,000
units
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,359,463 | 50,544,648 |
kWh
|
$0.047 |
Electricity Demand | $990,211 | 86,825 |
kW-mo/yr
|
$11.40 |
Electricity Fees | $(-101,782.2) | - |
|
- |
Natural Gas | $1,464,164 | 321,981 |
MMBtu
|
$4.55 |
TOTAL YEARLY COSTS | $4,712,055 | |||
RECOMMENDED SAVINGS* | $3,527,886 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $668,474 | $6,707,386 |
$452,100
9,619,143
kWh
|
$216,374
-
kW-mo/yr
|
- | - | |
02 | 2.4321: Upgrade obsolete equipment | $80,000 | $30,005 | - | - | - | $80,000 | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $56,915 | $6,958 |
$56,915
1,210,957
kWh
|
- | - | - | |
04 | 2.1221: Replace obsolete burners with more efficient ones | $43,724 | $145,930 | - | - |
$43,724
-
MMBtu
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $144,047 | $116,128 |
$144,047
3,064,830
kWh
|
- | - | - | |
06 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $2,534,726 | $11,184,200 |
$2,359,463
50,544,648
kWh
|
$990,211
-
kW-mo/yr
|
$(-814,947.9)
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $3,527,886 | $18,190,608 |
$3,012,525
64,439,577
kWh
|
$1,206,585
-
kW-mo/yr
|
$(-771,224.2)
-
MMBtu
|
$80,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs