Assessment Year 2023
Principal Product Air Handlers
NAICS 333415: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen
SIC 3585: Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment
Sales Range $50
M
to 100
M
# of Employees 230
Plant Area 12,850
ft2
Annual Production 461
units
Production Hrs. Annual 4,800
hrs
Location (State) Mississippi

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $223,483 2,379,600
kWh
Electricity Demand $11,665 5,884
kW-mo/yr
Electricity Fees $2,739 -
Natural Gas $23,055 1,974
MMBtu
Waste Disposal Costs
Water Usage $3,945 681
Tgal
TOTAL YEARLY COSTS $264,886
RECOMMENDED SAVINGS* $82,198 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7135: Install occupancy sensors $357 $1,634 $357
3,802
kWh
- -
02 2.9114: Use solar heat to make electricty $70,508 $548,100 $70,508
750,084
kWh
- -
03 2.7221: Lower temperature during the winter season and vice-versa $3,817 - $3,774
40,146
kWh
$43
-
kW-mo/yr
-
04 2.1321: Replace fossil fuel equipment with electrical equipment $2,092 $12,955 $(-973.2)
(-10,353)
kWh
- $3,065
-
MMBtu
05 2.6218: Turn off equipment when not in use $5,424 - $5,424
57,707
kWh
- -
TOTAL RECOMMENDED $82,198 $562,690 $79,090
841,386
kWh
$43
-
kW-mo/yr
$3,065
-
MMBtu
TOTAL IMPLEMENTED - - - - -