Assessment Year | 2010 |
---|---|
Principal Product | Lighting Fixtures |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 3087: Custom Compounding of Purchased Plastics Resins |
Sales Range | $10 M to 50M |
# of Employees | 63 |
Plant Area |
130,000
ft2
|
Annual Production | 5,400,000
units
|
Production Hrs. Annual | 6,300
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $304,127 | 6,248,400 |
kWh
|
$0.049 |
Electricity Demand | $239,161 | 16,874 |
kW-mo/yr
|
$14.17 |
Natural Gas | $38,313 | 36,623 |
MMBtu
|
$1.05 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $194,746 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.2314: Replace heat treating oven with more efficient unit | $112,791 | $264,425 |
$54,604
1,061,297
kWh
|
$56,521
-
kW-mo/yr
|
$1,666 | |
02 | 2.2314: Replace heat treating oven with more efficient unit | $30,120 | $217,605 |
$18,225
354,239
kWh
|
$11,450
-
kW-mo/yr
|
$445 | |
03 | 2.2314: Replace heat treating oven with more efficient unit | $29,394 | $103,215 |
$17,888
347,684
kWh
|
$11,072
-
kW-mo/yr
|
$434 | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,319 | $50,244 |
$7,999
155,464
kWh
|
$4,138
-
kW-mo/yr
|
$182 | |
05 | 2.7135: Install occupancy sensors | $5,041 | $300 |
$4,966
96,526
kWh
|
- | $75 | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,658 | $2,310 |
$676
13,145
kWh
|
$1,943
-
kW-mo/yr
|
$39 | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,423 | $378 |
$2,387
16,399
kWh
|
- | $36 | |
TOTAL RECOMMENDED | $194,746 | $638,477 |
$106,745
2,044,754
kWh
|
$85,124
-
kW-mo/yr
|
$2,877 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs