Assessment Year | 2009 |
---|---|
Principal Product | DOORS |
NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
SIC | 3231: Glass Products, Made of Purchased Glass |
Sales Range | $10 M to 50M |
# of Employees | 91 |
Plant Area |
240,000
ft2
|
Annual Production | 300,000
pieces
|
Production Hrs. Annual | 2,080
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $213,262 | 3,786,811 |
kWh
|
$0.056 |
Electricity Demand | $125,680 | 12,889 |
kW-mo/yr
|
$9.75 |
Electricity Fees | $15,764 | - |
|
- |
Natural Gas | $79,430 | 8,105 |
MMBtu
|
$9.80 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $67,490 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $39,601 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $27,889 | $39,913 |
$15,938
250,641
kWh
|
$11,539
-
kW-mo/yr
|
$412 | |
02 | 2.4239: Eliminate or reduce compressed air usage | $23,121 | $2,882 |
$22,779
358,231
kWh
|
- | $342 | |
03 | 2.7135: Install occupancy sensors | $9,234 | $4,004 |
$9,098
143,069
kWh
|
- | $136 | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,932 | $401 |
$3,873
60,925
kWh
|
- | $59 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,314 | $12,874 |
$1,756
27,613
kWh
|
$1,509
-
kW-mo/yr
|
$49 | |
TOTAL RECOMMENDED | $67,490 | $60,074 |
$53,444
840,479
kWh
|
$13,048
-
kW-mo/yr
|
$998 | ||
TOTAL IMPLEMENTED | $39,601 | $20,161 |
$37,506
589,838
kWh
|
$1,509
-
kW-mo/yr
|
$586 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs