Assessment Year 2006
Principal Product PVC resin and compound
NAICS 325211: Plastics Material and Resin Manufacturing
SIC 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers
Sales Range $100
M
to 500
M
# of Employees 174
Plant Area 1,089,000
ft2
Annual Production 1,220,000,000
lb
Production Hrs. Annual 8,736
hrs
Location (State) Mississippi

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $3,015,166 114,369,401
kWh
Electricity Demand $1,656,077 173,593
kW-mo/yr
Electricity Fees $239,433 -
Natural Gas $11,802,202 1,263,236
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $154,955 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $95,001

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $57,344 $3,269 $56,496
2,140,000
kWh
- $848 -
02 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $44,954 $113,910 $44,289
1,677,626
kWh
- $665 -
03 2.2135: Repair and eliminate steam leaks $33,575 $374 - - - $33,575
-
MMBtu
04 2.7142: Utilize higher efficiency lamps and/or ballasts $12,105 $51,885 $7,967
301,785
kWh
$3,959
-
kW-mo/yr
$179 -
05 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,082 $6,420 $2,352
89,100
kWh
$1,670
-
kW-mo/yr
$60 -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $2,895 $12,886 $1,631
61,799
kWh
$1,221
-
kW-mo/yr
$43 -
TOTAL RECOMMENDED $154,955 $188,744 $112,735
4,270,310
kWh
$6,850
-
kW-mo/yr
$1,795 $33,575
-
MMBtu
TOTAL IMPLEMENTED $95,001 $10,063 $58,848
2,229,100
kWh
$1,670
-
kW-mo/yr
$908 $33,575
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs