Assessment Year | 2006 |
---|---|
Principal Product | recycled paper |
NAICS | 322121: Paper (except Newsprint) Mills |
SIC | 2611: Pulp Mills |
Sales Range | $10 M to 50M |
# of Employees | 88 |
Plant Area |
550,000
ft2
|
Annual Production | 96,200
ton
|
Production Hrs. Annual | 7,392
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,353,170 | 68,207,832 |
kWh
|
$0.034 |
Electricity Demand | $739,507 | 129,284 |
kW-mo/yr
|
$5.72 |
Electricity Fees | $13,575,693 | - |
|
- |
Natural Gas | $1,546,515 | 222,197 |
MMBtu
|
$6.96 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $389,750 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $71,515 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $224,456 | $74,722 |
$21,383
619,793
kWh
|
$5,647
-
kW-mo/yr
|
$197,426 | - | |
02 | 2.2437: Recover waste heat from equipment | $42,324 | $29,520 | - | - | - |
$42,324
-
MMBtu
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $38,212 | $8,550 |
$3,590
104,052
kWh
|
$1,387
-
kW-mo/yr
|
$33,235 | - | |
04 | 2.1233: Analyze flue gas for proper air/fuel ratio | $28,523 | $2,000 | - | - | - |
$28,523
-
MMBtu
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $18,397 | $233 |
$1,808
52,397
kWh
|
- | $16,589 | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,825 | $34,509 |
$1,029
29,823
kWh
|
$292
-
kW-mo/yr
|
$9,504 | - | |
07 | 2.2136: Install / repair insulation on steam lines | $10,794 | $1,853 | - | - | - |
$10,794
-
MMBtu
|
|
08 | 2.2135: Repair and eliminate steam leaks | $9,158 | $169 | - | - | - |
$9,158
-
MMBtu
|
|
09 | 2.7229: Air condition only space necessary | $6,088 | $600 |
$428
12,312
kWh
|
$1,454
-
kW-mo/yr
|
$4,206 | - | |
10 | 2.7221: Lower temperature during the winter season and vice-versa | $973 | - |
$96
2,774
kWh
|
- | $877 | - | |
TOTAL RECOMMENDED | $389,750 | $152,156 |
$28,334
821,151
kWh
|
$8,780
-
kW-mo/yr
|
$261,837 |
$90,799
-
MMBtu
|
||
TOTAL IMPLEMENTED | $71,515 | $31,606 |
$1,808
52,397
kWh
|
- | $16,589 |
$53,118
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs