Assessment Year | 2005 |
---|---|
Principal Product | small gasoline engines |
NAICS | 336310: Motor Vehicle Gasoline Engine and Engine Parts Manufacturing |
SIC | 3714: Motor Vehicle Parts and Accessories |
Sales Range | $10 M to 50M |
# of Employees | 278 |
Plant Area |
186,277
ft2
|
Annual Production | 1,500,000
pieces
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $207,228 | 7,025,338 |
kWh
|
$0.029 |
Electricity Demand | $127,248 | 15,647 |
kW-mo/yr
|
$8.13 |
Electricity Fees | $27,323 | - |
|
- |
Natural Gas | $117,309 | 13,504 |
MMBtu
|
$8.69 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $26,997 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,615 | $42,772 |
$10,430
298,773
kWh
|
$7,736
-
kW-mo/yr
|
$(-2,551.0) | |
02 | 2.7111: Reduce illumination to minimum necessary levels | $5,962 | $54 |
$3,979
114,000
kWh
|
$2,956
-
kW-mo/yr
|
$(-973.0) | |
03 | 2.7124: Make a practice of turning off lights when not needed | $1,395 | $100 |
$932
26,710
kWh
|
$691
-
kW-mo/yr
|
$(-228.0) | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,133 | $2,724 |
$1,321
37,844
kWh
|
- | $(-188.0) | |
05 | 2.4221: Install compressor air intakes in coolest locations | $904 | $148 |
$469
13,427
kWh
|
$583
-
kW-mo/yr
|
$(-148.0) | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $743 | $2,475 |
$432
12,377
kWh
|
$432
-
kW-mo/yr
|
$(-121.0) | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,245 | $223 |
$1,453
41,617
kWh
|
- | $(-208.0) | |
TOTAL RECOMMENDED | $26,997 | $48,496 |
$19,016
544,748
kWh
|
$12,398
-
kW-mo/yr
|
$(-4,417.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs