Assessment Year | 2005 |
---|---|
Principal Product | Composite Structures |
NAICS | 336419: Other Guided Missile and Space Vehicle Parts and Auxiliary Equipment Manufacturing |
SIC | 3769: Guided Missile Space Vehicle Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 180 |
Plant Area |
320,000
ft2
|
Annual Production | 166
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $897,767 | 23,084,790 |
kWh
|
$0.039 |
Electricity Demand | $476,479 | 40,150 |
kW-mo/yr
|
$11.87 |
Electricity Fees | $21,814 | - |
|
- |
Natural Gas | $175,656 | 19,677 |
MMBtu
|
$8.93 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $144,856 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,724 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7124: Make a practice of turning off lights when not needed | $64,043 | $8,505 |
$63,097
1,622,437
kWh
|
- | $946 | |
02 | 2.7135: Install occupancy sensors | $32,940 | $298 |
$32,453
834,478
kWh
|
- | $487 | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,566 | $20,159 |
$14,147
363,759
kWh
|
$6,115
-
kW-mo/yr
|
$304 | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $16,492 | $8,838 |
$10,304
264,964
kWh
|
$5,944
-
kW-mo/yr
|
$244 | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,547 | $15,656 |
$6,450
165,855
kWh
|
- | $97 | |
06 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $2,712 | $1,848 |
$1,530
39,347
kWh
|
$1,142
-
kW-mo/yr
|
$40 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,158 | $1,871 |
$797
20,484
kWh
|
$344
-
kW-mo/yr
|
$17 | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $398 | $478 |
$97
2,507
kWh
|
$295
-
kW-mo/yr
|
$6 | |
TOTAL RECOMMENDED | $144,856 | $57,653 |
$128,875
3,313,831
kWh
|
$13,840
-
kW-mo/yr
|
$2,141 | ||
TOTAL IMPLEMENTED | $21,724 | $22,030 |
$14,944
384,243
kWh
|
$6,459
-
kW-mo/yr
|
$321 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs