Assessment Year | 2005 |
---|---|
Principal Product | printers |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3672: Printed Circuit Boards |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
650,000
ft2
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Tennessee |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $273,824 | 7,180,000 |
kWh
|
$0.038 |
Electricity Demand | $167,194 | 15,094 |
kW-mo/yr
|
$11.08 |
Electricity Fees | $30,871 | - |
|
- |
Natural Gas | $7,506 | 617 |
MMBtu
|
$12.17 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $332,424 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $331,929 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7124: Make a practice of turning off lights when not needed | $126,283 | $13,608 |
$118,022
3,109,930
kWh
|
- | $8,261 | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $61,735 | $79,029 |
$40,520
1,067,726
kWh
|
$17,176
-
kW-mo/yr
|
$4,039 | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $61,542 | $1,920 |
$40,399
1,064,540
kWh
|
$17,117
-
kW-mo/yr
|
$4,026 | |
04 | 2.7226: Use computer programs to optimize hvac performance | $38,704 | $8,800 |
$36,172
953,148
kWh
|
- | $2,532 | |
05 | 2.8121: Apply for tax-free status for energy purchases | $24,256 | $50 | - | - | $24,256 | |
06 | 2.7124: Make a practice of turning off lights when not needed | $11,055 | - |
$10,332
272,256
kWh
|
- | $723 | |
07 | 3.1191: Change procedures / equipment / operating conditions | $8,354 | - | - |
$7,807
-
kW-mo/yr
|
$547 | |
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $495 | $180 |
$463
12,200
kWh
|
- | $32 | |
TOTAL RECOMMENDED | $332,424 | $103,587 |
$245,908
6,479,800
kWh
|
$42,100
-
kW-mo/yr
|
$44,416 | ||
TOTAL IMPLEMENTED | $331,929 | $103,407 |
$245,445
6,467,600
kWh
|
$42,100
-
kW-mo/yr
|
$44,384 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs