| Assessment Year | 1998 |
|---|---|
| Principal Product | Battery Components |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 180 |
| Plant Area |
150,000
ft2
|
| Annual Production | 12,500,000
lb
|
| Production Hrs. Annual | 7,344
hrs
|
| Location (State) | Mississippi |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $512,246 | 16,691,970 |
kWh
|
$0.031 |
| Electricity Demand | $298,526 | 32,172 |
kW-mo/yr
|
$9.28 |
| Electricity Fees | $14,476 | - |
|
- |
| Natural Gas | $43,357 | 8,226 |
MMBtu
|
$5.27 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $110,363 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $33,432 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,208 | $9,250 |
$6,244
204,865
kWh
|
$3,813
-
kW-mo/yr
|
$151 | - | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,045 | $8,030 |
$3,986
130,715
kWh
|
- | $59 | - | - | |
| 03 | 2.2612: Use cooling tower water instead of refrigeration | $10,852 | $7,236 |
$10,692
350,821
kWh
|
- | $160 | - | - | |
| 04 | 2.3212: Optimize plant power factor | $11,323 | $4,875 | - | - | $11,323 | - | - | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $70,934 | $513,675 |
$67,021
2,198,124
kWh
|
$2,864
-
kW-mo/yr
|
$1,049 | - | - | |
| 06 | 3.1191: Change procedures / equipment / operating conditions | $1,049 | $1,235 | - | - | - | - | $1,049 | |
| 07 | 3.6124: Burn waste oil for heat | $1,952 | $2,745 |
$1,430
46,893
kWh
|
- | $22 |
$500
-
gal
|
- | |
| TOTAL RECOMMENDED | $110,363 | $547,046 |
$89,373
2,931,418
kWh
|
$6,677
-
kW-mo/yr
|
$12,764 |
$500
-
gal
|
$1,049 | ||
| TOTAL IMPLEMENTED | $33,432 | $22,596 |
$16,936
555,686
kWh
|
$3,813
-
kW-mo/yr
|
$11,634 | - | $1,049 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Other Liquid (haz) Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs