Assessment Year | 1997 |
---|---|
Principal Product | white bread and buns |
NAICS |
n/a
|
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $10 M to 50M |
# of Employees | 103 |
Plant Area |
95,000
ft2
|
Annual Production | 65,000,000
lb
|
Production Hrs. Annual | 7,592
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $82,220 | 4,472,450 |
kWh
|
$0.018 |
Electricity Demand | $36,763 | 8,386 |
kW-mo/yr
|
$4.38 |
Electricity Fees | $127,914 | - |
|
- |
Natural Gas | $206,298 | 41,529 |
MMBtu
|
$4.97 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $53,714 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $19,768 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Other Liquid (haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $9,330 | $5,625 | - |
$9,330
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,033 | $5,664 |
$714
67,116
kWh
|
$861
-
kW-mo/yr
|
$1,458 | - | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $1,313 | $90 |
$326
30,481
kWh
|
$323
-
kW-mo/yr
|
$664 | - | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,271 | $6,134 |
$420
39,566
kWh
|
- | $851 | - | - | - | |
05 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $20,680 | $19,019 | - | - | - |
$20,680
-
MMBtu
|
- | - | |
06 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $9,125 | $6,500 | - | - | - | - | - | $9,125 | |
07 | 3.6124: Burn waste oil for heat | $8,264 | $1,995 | - | - | - |
$214
-
MMBtu
|
$8,050
-
gal
|
- | |
08 | 3.4155: Meter waste water | $698 | $665 | - | - | - | - | - | $698 | |
TOTAL RECOMMENDED | $53,714 | $45,692 |
$1,460
137,163
kWh
|
$10,514
-
kW-mo/yr
|
$2,973 |
$20,894
-
MMBtu
|
$8,050
-
gal
|
$9,823 | ||
TOTAL IMPLEMENTED | $19,768 | $12,215 |
$326
30,481
kWh
|
$9,653
-
kW-mo/yr
|
$664 | - | - | $9,125 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Other Liquid (haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs