Assessment Year | 1996 |
---|---|
Principal Product | pants |
NAICS |
n/a
|
SIC | 2325: Men's and Boys' Separate Trousers and Slacks |
Sales Range | $50 M to 100M |
# of Employees | 300 |
Plant Area |
219,000
ft2
|
Annual Production | 6,875,000
pieces
|
Production Hrs. Annual | 4,165
hrs
|
Location (State) | Mississippi |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $137,701 | 3,761,430 |
kWh
|
$0.037 |
Electricity Demand | $83,315 | 13,343 |
kW-mo/yr
|
$6.24 |
Electricity Fees | $4,496 | - |
|
- |
Natural Gas | $45,183 | 10,006 |
MMBtu
|
$4.52 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $18,651 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,192 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,116 | $10,500 |
$1,291
41,618
kWh
|
$1,825
-
kW-mo/yr
|
- | - | - | - | |
02 | 2.7227: Use water on air conditioning exchanger to improve heat transfer and increase air conditioner efficiency | $1,213 | $5,100 |
$1,360
43,962
kWh
|
$211
-
kW-mo/yr
|
- |
$(-358.0)
-
Tgal
|
- | - | |
03 | 2.4312: Improve lubrication practices | $1,076 | $150 |
$588
18,757
kWh
|
$488
-
kW-mo/yr
|
- | - | - | - | |
04 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $2,888 | $3,000 |
$2,888
93,200
kWh
|
- | - | - | - | - | |
05 | 2.7241: Install outside air damper / economizer on hvac unit | $2,424 | $7,000 |
$2,424
78,253
kWh
|
- | - | - | - | - | |
06 | 2.8114: Change rate schedules or other changes in utility service | $3,866 | - | - | - | $3,866 | - | - | - | |
07 | 3.7196: Use re-usable filters | $648 | $1,080 | - | - | - | - | - | $648 | |
08 | 3.5313: Increase amount of waste recovered for resale | $3,420 | - | - | - | - | - |
$3,420
-
lb
|
- | |
TOTAL RECOMMENDED | $18,651 | $26,830 |
$8,551
275,790
kWh
|
$2,524
-
kW-mo/yr
|
$3,866 |
$(-358.0)
-
Tgal
|
$3,420
-
lb
|
$648 | ||
TOTAL IMPLEMENTED | $4,192 | $10,650 |
$1,879
60,375
kWh
|
$2,313
-
kW-mo/yr
|
- | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Water Disposal Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs