| Assessment Year | 1992 |
|---|---|
| Principal Product | CIRCUIT BREAKERS |
| NAICS |
n/a
|
| SIC | 3679: Electronic Components, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 400 |
| Plant Area |
n/a
|
| Annual Production | 1,520,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Missouri |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $625,758 | 10,556,565 |
kWh
|
$0.059 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $96,088 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $49,637 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $47,665 | $29,000 |
$82,015
1,383,939
kWh
|
$(-34,350.0)
-
MMBtu
|
|
| 02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $5,312 | - |
$9,252
156,213
kWh
|
$(-3,940.0)
-
MMBtu
|
|
| 03 | 2.4133: Use most efficient type of electric motors | $959 | - |
$959
16,120
kWh
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,537 | $958 |
$4,537
76,495
kWh
|
- | |
| 05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,972 | $5,350 |
$1,972
33,411
kWh
|
- | |
| 06 | 2.4133: Use most efficient type of electric motors | $1,845 | - |
$1,845
31,067
kWh
|
- | |
| 07 | 2.2511: Insulate bare equipment | $29,176 | $3,956 |
$29,176
492,380
kWh
|
- | |
| 08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,123 | $3,321 |
$2,123
36,928
kWh
|
- | |
| 09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,499 | $50 |
$2,499
42,204
kWh
|
- | |
| TOTAL RECOMMENDED | $96,088 | $42,635 |
$134,378
2,268,757
kWh
|
$(-38,290.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $49,637 | $34,350 |
$83,987
1,417,350
kWh
|
$(-34,350.0)
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs