Assessment Year | 1990 |
---|---|
Principal Product | CHARCOAL & LIGHTER FLUID |
NAICS |
n/a
|
SIC | 2861: Gum and Wood Chemicals |
Sales Range | $10 M to 50M |
# of Employees | 75 |
Plant Area |
n/a
|
Annual Production | 80,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Missouri |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $92,850 | 2,053,927 |
kWh
|
$0.045 |
LPG | $164,634 | 53,861 |
MMBtu
|
$3.06 |
Fuel Oil #2 | $2,720 | 560 |
MMBtu
|
$4.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,197 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,262 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | LPG Savings |
---|---|---|---|---|---|---|
01 | 2.2511: Insulate bare equipment | $2,439 | $3,511 | - |
$2,439
-
MMBtu
|
|
02 | 2.4131: Size electric motors for peak operating efficiency | $19,712 | $9,886 |
$19,712
436,401
kWh
|
- | |
03 | 2.2531: Re-size charging openings or add movable cover or door | $6,935 | $351 | - |
$6,935
-
MMBtu
|
|
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,436 | $3,500 |
$2,436
53,927
kWh
|
- | |
05 | 2.1123: Install automatic stack damper | $585 | $175 | - |
$585
-
MMBtu
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $90 | $72 |
$90
2,052
kWh
|
- | |
TOTAL RECOMMENDED | $32,197 | $17,495 |
$22,238
492,380
kWh
|
$9,959
-
MMBtu
|
||
TOTAL IMPLEMENTED | $25,262 | $17,144 |
$22,238
492,380
kWh
|
$3,024
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs