| Assessment Year | 2026 |
|---|---|
| Principal Product | Azipod/Turbocharger |
| NAICS | 334513: Instruments and Related Products Manufacturing for Measuring, Displaying, and Controlling Industrial |
| SIC | 3823: Industrial Instruments for Measurement, Display, and Control of Process Variables; and Related Products |
| Sales Range | $100 M to 500M |
| # of Employees | 80 |
| Plant Area |
40,000
ft2
|
| Annual Production | 500
units
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $40,285 | 665,826 |
kWh
|
$0.061 |
| Electricity Demand | $40,324 | 2,672 |
kW-mo/yr
|
$15.09 |
| Electricity Fees | $20,326 | - |
|
- |
| TOTAL YEARLY COSTS | $100,935 | |||
| RECOMMENDED SAVINGS* | $16,570 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $1,600 | - |
$705
11,555
kWh
|
$895
-
kW-mo/yr
|
|
| 02 | 2.7224: Reduce space conditioning during non-working hours | $1,285 | - |
$1,285
21,060
kWh
|
- | |
| 03 | 2.7221: Lower temperature during the winter season and vice-versa | $6,557 | - |
$2,890
47,379
kWh
|
$3,667
-
kW-mo/yr
|
|
| 04 | 2.7135: Install occupancy sensors | $2,919 | $5,000 |
$1,286
21,090
kWh
|
$1,633
-
kW-mo/yr
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,209 | $10,510 |
$1,855
30,416
kWh
|
$2,354
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $16,570 | $15,510 |
$8,021
131,500
kWh
|
$8,549
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs