Assessment Year 2025
Principal Product Beverage Distribution company
NAICS 424810: Beer and Ale Merchant Wholesalers
SIC 5181: Beer and Ale
Sales Range $100
M
to 500
M
# of Employees 360
Plant Area 312,000
ft2
Annual Production 30,000,000
units
Production Hrs. Annual 2,860
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $467,294 2,778,680
kWh
Electricity Demand $94,127 6,102
kW-mo/yr
Electricity Fees $68,543 -
TOTAL YEARLY COSTS $629,964
RECOMMENDED SAVINGS* $284,178 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7221: Lower temperature during the winter season and vice-versa $16,554 - $11,957
71,175
kWh
$4,597
-
kW-mo/yr
02 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas $31,123 $711 $27,652
164,594
kWh
$3,471
-
kW-mo/yr
03 2.7229: Air condition only space necessary $47,824 $1,440 $34,527
205,516
kWh
$13,297
-
kW-mo/yr
04 2.3132: Recharge batteries on during off-peak demand periods $9,626 $320 - $9,626
-
kW-mo/yr
05 2.6218: Turn off equipment when not in use $4,820 $2,600 $4,820
28,693
kWh
-
06 2.7134: Use photocell controls $742 $720 $492
2,928
kWh
$250
-
kW-mo/yr
07 2.7232: Replace existing hvac unit with high efficiency model $26,731 $45,465 $18,833
112,104
kWh
$7,898
-
kW-mo/yr
08 2.9114: Use solar heat to make electricty $146,758 $671,919 $138,675
825,445
kWh
$8,083
-
kW-mo/yr
TOTAL RECOMMENDED $284,178 $723,175 $236,956
1,410,455
kWh
$47,222
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs