ITAC Assessment: MI0456
ITAC logo
ITAC Assessment: MI0456
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2025
Principal Product Aircraft Integrated Drive Generators
NAICS 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing
SIC 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified
Sales Range $100
M
to 500
M
# of Employees 202
Plant Area 94,000
ft2
Annual Production 10,000
pieces
Production Hrs. Annual 4,420
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $162,940 2,728,800
kWh
Electricity Demand $155,456 10,728
kW-mo/yr
Electricity Fees $84,539 -
TOTAL YEARLY COSTS $402,935
RECOMMENDED SAVINGS* $76,867 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7221: Lower temperature during the winter season and vice-versa $24,997 $1,580 $23,702
395,037
kWh
$1,295
-
kW-mo/yr
02 2.4239: Eliminate or reduce compressed air usage $10,605 $780 $7,601
126,680
kWh
$3,004
-
kW-mo/yr
03 2.6218: Turn off equipment when not in use $27,034 $2,400 $27,034
450,569
kWh
-
04 2.7224: Reduce space conditioning during non-working hours $2,360 $700 $2,360
39,334
kWh
-
05 2.7245: Use direct air supply to exhaust hoods $2,423 $3,171 $1,467
24,448
kWh
$956
-
kW-mo/yr
06 2.7232: Replace existing hvac unit with high efficiency model $9,448 $31,295 $5,709
95,160
kWh
$3,739
-
kW-mo/yr
TOTAL RECOMMENDED $76,867 $39,926 $67,873
1,131,228
kWh
$8,994
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs