Assessment Year | 2025 |
---|---|
Principal Product | Aluminum Extrusion / Mill Finish |
NAICS | 331318: Other Aluminum Rolling, Drawing, and Extruding |
SIC | 3354: Aluminum Extruded Products |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
423,916
ft2
|
Annual Production | 12,000,000
lb
|
Production Hrs. Annual | 4,000
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $449,543 | 2,120,978 |
kWh
|
$0.21 |
Electricity Demand | $108,095 | 9,444 |
kW-mo/yr
|
$11.45 |
Electricity Fees | $5,400 | - |
|
- |
TOTAL YEARLY COSTS | $563,037 | |||
RECOMMENDED SAVINGS* | $115,979 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $46,100 | $45,007 | - |
$46,100
-
kW-mo/yr
|
- | |
02 | 2.8114: Change rate schedules or other changes in utility service | $24,930 | $3,200 | - | - | $24,930 | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $20,861 | $35,685 |
$18,698
88,200
kWh
|
$2,163
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $17,287 | $1,620 |
$12,068
56,923
kWh
|
$5,219
-
kW-mo/yr
|
- | |
05 | 2.4239: Eliminate or reduce compressed air usage | $5,478 | $80 |
$4,887
23,051
kWh
|
$591
-
kW-mo/yr
|
- | |
06 | 2.7135: Install occupancy sensors | $1,323 | $1,578 |
$1,323
6,240
kWh
|
- | - | |
TOTAL RECOMMENDED | $115,979 | $87,170 |
$36,976
174,414
kWh
|
$54,073
-
kW-mo/yr
|
$24,930 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs