Assessment Year | 2024 |
---|---|
Principal Product | Pharmaceuticals |
NAICS | 325412: Pharmaceutical Preparation Manufacturing |
SIC | 2834: Pharmaceutical Preparations |
Sales Range | $100 M to 500M |
# of Employees | 170 |
Plant Area |
480,000
ft2
|
Annual Production | 1,000,000
pieces
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,852,531 | 14,191,320 |
kWh
|
$0.20 |
Electricity Demand | $329,995 | 34,264 |
kW-mo/yr
|
$9.63 |
Electricity Fees | $190,809 | - |
|
- |
TOTAL YEARLY COSTS | $3,373,335 | |||
RECOMMENDED SAVINGS* | $837,486 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.2622: Replace existing chiller with high efficiency model | $427,475 | $602,500 |
$400,084
1,990,468
kWh
|
$27,391
-
kW-mo/yr
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $217,248 | $42,472 |
$203,331
1,011,598
kWh
|
$13,917
-
kW-mo/yr
|
- | |
03 | 2.8123: Pay utility bills on time | $80,165 | - | - | - | $80,165 | |
04 | 2.3212: Optimize plant power factor | $46,588 | $99,444 | - |
$46,588
-
kW-mo/yr
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $32,574 | $11,027 |
$30,487
151,679
kWh
|
$2,087
-
kW-mo/yr
|
- | |
06 | 2.8114: Change rate schedules or other changes in utility service | $19,584 | $150 | - | - | $19,584 | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,583 | $5,793 |
$9,905
49,281
kWh
|
$678
-
kW-mo/yr
|
- | |
08 | 2.7135: Install occupancy sensors | $3,269 | $2,860 |
$3,269
16,265
kWh
|
- | - | |
TOTAL RECOMMENDED | $837,486 | $764,246 |
$647,076
3,219,291
kWh
|
$90,661
-
kW-mo/yr
|
$99,749 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs