| Assessment Year | 2022 |
|---|---|
| Principal Product | Cigars |
| NAICS | 312230: Tobacco Manufacturing |
| SIC | 2121: Cigars |
| Sales Range | $10 M to 50M |
| # of Employees | 400 |
| Plant Area |
270,000
ft2
|
| Annual Production | 800,000,000
pieces
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Puerto Rico |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,933,669 | 8,406,767 |
kWh
|
$0.23 |
| Electricity Demand | $116,890 | 13,364 |
kW-mo/yr
|
$8.75 |
| Electricity Fees | $5,400 | - |
|
- |
| TOTAL YEARLY COSTS | $2,055,959 | |||
| RECOMMENDED SAVINGS* | $252,900 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $126,797 | $24,547 |
$117,834
512,322
kWh
|
$8,963
-
kW-mo/yr
|
- | |
| 02 | 3.1161: Eliminate/reduce an operation | $73,444 | $22,400 |
$68,253
296,750
kWh
|
$5,191
-
kW-mo/yr
|
- | |
| 03 | 2.4238: Do not use compressed air for personal cooling | $9,634 | $2,055 |
$8,952
38,923
kWh
|
$682
-
kW-mo/yr
|
- | |
| 04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $2,603 | $6,042 | - | - | $2,603 | |
| 05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $40,422 | $1,980 |
$31,206
135,680
kWh
|
$9,216
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $252,900 | $57,024 |
$226,245
983,675
kWh
|
$24,052
-
kW-mo/yr
|
$2,603 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs