| Assessment Year | 2022 |
|---|---|
| Principal Product | Food Products |
| NAICS | 311999: All Other Miscellaneous Food Manufacturing |
| SIC | 2099: Food Preparations, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 180 |
| Plant Area |
385,000
ft2
|
| Annual Production | 25,000,000
pieces
|
| Production Hrs. Annual | 3,000
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $311,133 | 5,099,256 |
kWh
|
$0.061 |
| Electricity Demand | $116,364 | 12,708 |
kW-mo/yr
|
$9.16 |
| Electricity Fees | $35,282 | - |
|
- |
| Natural Gas | $32,103 | 8,116 |
MMBtu
|
$3.96 |
| TOTAL YEARLY COSTS | $494,882 | |||
| RECOMMENDED SAVINGS* | $49,917 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $18,401 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7425: Clean or color roof to reduce solar load | $13,967 | $34,488 |
$6,696
109,770
kWh
|
$7,271
-
kW-mo/yr
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,855 | $11,226 |
$6,518
106,853
kWh
|
$1,337
-
kW-mo/yr
|
- | |
| 03 | 2.7135: Install occupancy sensors | $5,931 | $3,518 |
$5,931
97,229
kWh
|
- | - | |
| 04 | 2.7221: Lower temperature during the winter season and vice-versa | $5,597 | $320 |
$4,571
74,941
kWh
|
$1,026
-
kW-mo/yr
|
- | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $5,218 | $1,980 |
$1,976
32,398
kWh
|
$3,242
-
kW-mo/yr
|
- | |
| 06 | 2.3132: Recharge batteries on during off-peak demand periods | $4,615 | $1,827 | - |
$4,615
-
kW-mo/yr
|
- | |
| 07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,897 | $1,980 |
$1,187
19,463
kWh
|
$2,710
-
kW-mo/yr
|
- | |
| 08 | 2.8112: Combine utility meters | $2,837 | $100 | - | - | $2,837 | |
| TOTAL RECOMMENDED | $49,917 | $55,439 |
$26,879
440,654
kWh
|
$20,201
-
kW-mo/yr
|
$2,837 | ||
| TOTAL IMPLEMENTED | $18,401 | $16,571 |
$12,449
204,082
kWh
|
$5,952
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs