Assessment Year | 2019 |
---|---|
Principal Product | Automotive Accessories |
NAICS | 334310: Audio and Video Equipment Manufacturing |
SIC | 3651: Household Audio and Video Equipment |
Sales Range | $100 M to 500M |
# of Employees | 300 |
Plant Area |
180,600
ft2
|
Annual Production | 6,000,000
pieces
|
Production Hrs. Annual | 2,601
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $240,815 | 4,770,409 |
kWh
|
$0.050 |
Electricity Demand | $141,323 | 12,914 |
kW-mo/yr
|
$10.94 |
Electricity Fees | $81,804 | - |
|
- |
TOTAL YEARLY COSTS | $463,942 | |||
RECOMMENDED SAVINGS* | $71,526 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $50,590 | $93,076 |
$25,049
500,979
kWh
|
$25,541
-
kW-mo/yr
|
|
02 | 2.7111: Reduce illumination to minimum necessary levels | $4,035 | $1,115 |
$4,035
80,693
kWh
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,152 | $120 |
$3,368
67,363
kWh
|
$1,784
-
kW-mo/yr
|
|
04 | 2.7134: Use photocell controls | $3,435 | $4,831 |
$3,435
68,706
kWh
|
- | |
05 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $3,258 | $2,265 |
$3,499
69,971
kWh
|
$(-241.0)
-
kW-mo/yr
|
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,463 | $1,980 |
$959
19,188
kWh
|
$504
-
kW-mo/yr
|
|
07 | 2.4323: Use optimum size and capacity equipment | $1,903 | $4,341 |
$1,159
23,174
kWh
|
$744
-
kW-mo/yr
|
|
08 | 2.7135: Install occupancy sensors | $1,690 | $1,188 |
$1,690
33,804
kWh
|
- | |
TOTAL RECOMMENDED | $71,526 | $108,916 |
$43,194
863,878
kWh
|
$28,332
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs