Assessment Year | 2019 |
---|---|
Principal Product | Utility Connectors |
NAICS | 335931: Current-Carrying Wiring Device Manufacturing |
SIC | 3643: Current-Carrying Wiring Devices |
Sales Range | $50 M to 100M |
# of Employees | 325 |
Plant Area |
142,000
ft2
|
Annual Production | 16,000,000
pieces
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $423,000 | 8,962,050 |
kWh
|
$0.047 |
Electricity Demand | $218,181 | 21,131 |
kW-mo/yr
|
$10.33 |
Electricity Fees | $119,586 | - |
|
- |
Natural Gas | $6,558 | 1,119 |
MMBtu
|
$5.86 |
TOTAL YEARLY COSTS | $767,325 | |||
RECOMMENDED SAVINGS* | $47,443 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,703 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $18,306 | $3,600 |
$18,306
389,497
kWh
|
- | - | |
02 | 2.9112: Use solar heat to heat water | $11,005 | $67,338 |
$7,691
163,639
kWh
|
$3,314
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,689 | $1,980 |
$3,584
76,248
kWh
|
$1,105
-
kW-mo/yr
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,177 | $2,193 |
$2,917
62,065
kWh
|
$1,260
-
kW-mo/yr
|
- | |
05 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $3,870 | $8,000 |
$3,870
82,351
kWh
|
- | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,575 | $160 |
$1,966
41,824
kWh
|
$609
-
kW-mo/yr
|
- | |
07 | 2.6127: Maintain air filters by cleaning or replacement | $1,267 | $1,195 |
$885
18,835
kWh
|
$382
-
kW-mo/yr
|
- | |
08 | 2.1233: Analyze flue gas for proper air/fuel ratio | $996 | $2,040 | - | - |
$996
-
MMBtu
|
|
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $558 | $1,773 |
$558
11,875
kWh
|
- | - | |
TOTAL RECOMMENDED | $47,443 | $88,279 |
$39,777
846,334
kWh
|
$6,670
-
kW-mo/yr
|
$996
-
MMBtu
|
||
TOTAL IMPLEMENTED | $31,703 | $16,975 |
$28,611
608,755
kWh
|
$2,096
-
kW-mo/yr
|
$996
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs