Assessment Year | 2018 |
---|---|
Principal Product | Cosmetic Products |
NAICS | 325611: Soap and Other Detergent Manufacturing |
SIC | 2844: Perfumes, Cosmetics, and Other Toilet Preparations |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
200,000
ft2
|
Annual Production | 20,000,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $271,987 | 5,540,000 |
kWh
|
$0.049 |
Electricity Demand | $118,114 | 9,404 |
kW-mo/yr
|
$12.56 |
Electricity Fees | $67,345 | - |
|
- |
TOTAL YEARLY COSTS | $457,446 | |||
RECOMMENDED SAVINGS* | $104,130 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $52,016 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.2628: Utilize a less expensive cooling method | $32,062 | $127,500 |
$19,521
397,578
kWh
|
$6,841
-
kW-mo/yr
|
$5,700 | |
02 | 2.7425: Clean or color roof to reduce solar load | $22,847 | $63,840 |
$16,918
344,568
kWh
|
$5,929
-
kW-mo/yr
|
- | |
03 | 2.7496: Install partitions to reduce size of conditioned space | $19,041 | $25,680 |
$14,100
287,183
kWh
|
$4,941
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,135 | $1,660 |
$8,256
168,146
kWh
|
$2,879
-
kW-mo/yr
|
- | |
05 | 2.7221: Lower temperature during the winter season and vice-versa | $5,680 | $40 |
$4,203
85,604
kWh
|
$1,477
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,307 | $13,190 |
$1,746
35,558
kWh
|
$2,561
-
kW-mo/yr
|
- | |
07 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $3,824 | $5,032 |
$2,712
55,243
kWh
|
$1,112
-
kW-mo/yr
|
- | |
08 | 2.7134: Use photocell controls | $2,086 | $5,544 |
$2,086
42,491
kWh
|
- | - | |
09 | 2.4239: Eliminate or reduce compressed air usage | $1,121 | $1,501 |
$795
16,195
kWh
|
$326
-
kW-mo/yr
|
- | |
10 | 2.7134: Use photocell controls | $1,016 | $2,773 |
$456
9,279
kWh
|
$560
-
kW-mo/yr
|
- | |
11 | 2.2511: Insulate bare equipment | $1,011 | $206 |
$749
15,250
kWh
|
$262
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $104,130 | $246,966 |
$71,542
1,457,095
kWh
|
$26,888
-
kW-mo/yr
|
$5,700 | ||
TOTAL IMPLEMENTED | $52,016 | $93,580 |
$37,172
757,084
kWh
|
$14,844
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs