Assessment Year | 2014 |
---|---|
Principal Product | Boats |
NAICS | 336612: Boat Building |
SIC | 3732: Boat Building and Repairing |
Sales Range | $100 M to 500M |
# of Employees | 420 |
Plant Area |
500,000
ft2
|
Annual Production | 1,200
units
|
Production Hrs. Annual | 3,276
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $197,004 | 2,807,620 |
kWh
|
$0.070 |
Electricity Demand | $72,941 | 13,398 |
kW-mo/yr
|
$5.44 |
Electricity Fees | $14,647 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $90,412 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $46,182 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,276 | $162,540 |
$17,337
247,665
kWh
|
$4,939
-
kW-mo/yr
|
|
02 | 2.7145: Install skylights | $21,450 | $52,105 |
$16,511
235,872
kWh
|
$4,939
-
kW-mo/yr
|
|
03 | 2.6218: Turn off equipment when not in use | $13,922 | $6,600 |
$10,835
154,792
kWh
|
$3,087
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,020 | $1,660 |
$6,951
99,927
kWh
|
$2,069
-
kW-mo/yr
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,032 | $6,480 |
$6,622
94,608
kWh
|
$1,410
-
kW-mo/yr
|
|
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,062 | $80 |
$3,442
49,168
kWh
|
$620
-
kW-mo/yr
|
|
07 | 2.4239: Eliminate or reduce compressed air usage | $3,236 | $5,000 |
$2,584
36,484
kWh
|
$652
-
kW-mo/yr
|
|
08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,278 | $1,660 |
$1,390
19,860
kWh
|
$888
-
kW-mo/yr
|
|
09 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,716 | $1,660 |
$1,096
15,661
kWh
|
$620
-
kW-mo/yr
|
|
10 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,326 | $80 |
$966
13,798
kWh
|
$360
-
kW-mo/yr
|
|
11 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $789 | $1,660 |
$605
8,639
kWh
|
$184
-
kW-mo/yr
|
|
12 | 2.4231: Reduce the pressure of compressed air to the minimum required | $649 | $80 |
$485
6,935
kWh
|
$164
-
kW-mo/yr
|
|
13 | 2.4231: Reduce the pressure of compressed air to the minimum required | $610 | $80 |
$420
6,001
kWh
|
$190
-
kW-mo/yr
|
|
14 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $525 | $1,660 |
$407
5,809
kWh
|
$118
-
kW-mo/yr
|
|
15 | 2.4231: Reduce the pressure of compressed air to the minimum required | $521 | $80 |
$344
4,915
kWh
|
$177
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $90,412 | $241,425 |
$69,995
1,000,134
kWh
|
$20,417
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $46,182 | $65,805 |
$35,201
503,069
kWh
|
$10,981
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs