| Assessment Year | 2013 |
|---|---|
| Principal Product | Pharmacuticals |
| NAICS | 325412: Pharmaceutical Preparation Manufacturing |
| SIC | 2834: Pharmaceutical Preparations |
| Sales Range | $10 M to 50M |
| # of Employees | 300 |
| Plant Area |
240,000
ft2
|
| Annual Production | 10,000,000
pieces
|
| Production Hrs. Annual | 7,488
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $731,608 | 14,720,870 |
kWh
|
$0.050 |
| Electricity Demand | $331,569 | 24,758 |
kW-mo/yr
|
$13.39 |
| Electricity Fees | $161,351 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $340,867 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $126,302 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2628: Utilize a less expensive cooling method | $174,761 | $506,800 |
$122,286
2,445,728
kWh
|
$52,475
-
kW-mo/yr
|
|
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $53,448 | $80 |
$37,393
747,859
kWh
|
$16,055
-
kW-mo/yr
|
|
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $43,154 | $52,122 |
$30,192
603,832
kWh
|
$12,962
-
kW-mo/yr
|
|
| 04 | 2.7135: Install occupancy sensors | $36,919 | $2,300 |
$25,833
516,672
kWh
|
$11,086
-
kW-mo/yr
|
|
| 05 | 2.7425: Clean or color roof to reduce solar load | $22,448 | $1,680 |
$15,707
314,132
kWh
|
$6,741
-
kW-mo/yr
|
|
| 06 | 2.7425: Clean or color roof to reduce solar load | $4,676 | $1,660 |
$1,452
29,032
kWh
|
$3,224
-
kW-mo/yr
|
|
| 07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,885 | $4,840 |
$2,015
40,050
kWh
|
$870
-
kW-mo/yr
|
|
| 08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,576 | $80 |
$1,291
25,828
kWh
|
$1,285
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $340,867 | $569,562 |
$236,169
4,723,133
kWh
|
$104,698
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $126,302 | $55,622 |
$86,035
1,720,683
kWh
|
$40,267
-
kW-mo/yr
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs