Assessment Year | 2013 |
---|---|
Principal Product | Adhesives and Sealants |
NAICS | 325520: Adhesive Manufacturing |
SIC | 2891: Adhesives and Sealants |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
75,000
ft2
|
Annual Production | 156,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $87,146 | 1,665,600 |
kWh
|
$0.052 |
Electricity Demand | $45,125 | 4,472 |
kW-mo/yr
|
$10.09 |
Electricity Fees | $22,642 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $53,093 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,710 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $27,762 | $68,060 |
$20,003
400,052
kWh
|
$7,759
-
kW-mo/yr
|
|
02 | 2.6218: Turn off equipment when not in use | $4,361 | $1,800 |
$3,140
62,790
kWh
|
$1,221
-
kW-mo/yr
|
|
03 | 2.7145: Install skylights | $3,415 | $2,780 |
$2,053
41,059
kWh
|
$1,362
-
kW-mo/yr
|
|
04 | 2.7425: Clean or color roof to reduce solar load | $3,133 | $2,600 |
$2,255
45,091
kWh
|
$878
-
kW-mo/yr
|
|
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,214 | $80 |
$1,925
38,491
kWh
|
$1,289
-
kW-mo/yr
|
|
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,120 | $3,520 |
$2,247
44,928
kWh
|
$873
-
kW-mo/yr
|
|
07 | 2.7221: Lower temperature during the winter season and vice-versa | $2,411 | $80 |
$1,735
34,700
kWh
|
$676
-
kW-mo/yr
|
|
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,368 | $2,340 |
$1,520
30,402
kWh
|
$848
-
kW-mo/yr
|
|
09 | 2.7135: Install occupancy sensors | $2,117 | $446 |
$1,522
30,433
kWh
|
$595
-
kW-mo/yr
|
|
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,192 | $1,660 |
$225
4,499
kWh
|
$967
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $53,093 | $83,366 |
$36,625
732,445
kWh
|
$16,468
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $16,710 | $6,846 |
$10,600
211,972
kWh
|
$6,110
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs