Assessment Year | 2010 |
---|---|
Principal Product | toilet tissue |
NAICS | 322121: Paper (except Newsprint) Mills |
SIC | 2621: Paper Mills |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
240,000
ft2
|
Annual Production | 20,000
ton
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,782,797 | 39,116,945 |
kWh
|
$0.071 |
Electricity Demand | $281,484 | 70,313 |
kW-mo/yr
|
$4.00 |
Electricity Fees | $390,029 | - |
|
- |
Natural Gas | $1,132,450 | 187,045 |
MMBtu
|
$6.05 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $700,361 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $606,228 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 3.6112: Use filter and drying oven to reduce sludge volume | $500,499 | - | - | - | - | $500,499 | |
02 | 2.3137: Use power during off-peak periods | $45,276 | $2,000 | - |
$45,276
-
kW-mo/yr
|
- | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $42,782 | $60 |
$38,181
477,264
kWh
|
$4,601
-
kW-mo/yr
|
- | - | |
04 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $38,905 | - | - | - |
$38,905
-
MMBtu
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $29,420 | $920 |
$26,458
330,730
kWh
|
$2,962
-
kW-mo/yr
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $26,600 | $1,920 | - |
$26,600
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,952 | $3,680 |
$9,301
116,268
kWh
|
$651
-
kW-mo/yr
|
- | - | |
08 | 2.2136: Install / repair insulation on steam lines | $3,050 | $2,904 | - | - |
$3,050
-
MMBtu
|
- | |
09 | 2.2136: Install / repair insulation on steam lines | $2,341 | $1,800 | - | - |
$2,341
-
MMBtu
|
- | |
10 | 2.1233: Analyze flue gas for proper air/fuel ratio | $1,536 | $1,500 | - | - |
$1,536
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $700,361 | $14,784 |
$73,940
924,262
kWh
|
$80,090
-
kW-mo/yr
|
$45,832
-
MMBtu
|
$500,499 | ||
TOTAL IMPLEMENTED | $606,228 | $9,104 |
$64,639
807,994
kWh
|
$34,163
-
kW-mo/yr
|
$6,927
-
MMBtu
|
$500,499 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs