Assessment Year | 2009 |
---|---|
Principal Product | Pacemakers |
NAICS | 334510: Electromedical and Electrotherapeutic Apparatus Manufacturing |
SIC | 3845: Electromedical and Electrotherapeutic Apparatus |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
125,000
ft2
|
Annual Production | 25,000
units
|
Production Hrs. Annual | 4,590
hrs
|
Location (State) | Puerto Rico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,770,160 | 15,493,680 |
kWh
|
$0.18 |
Electricity Demand | $219,483 | 28,504 |
kW-mo/yr
|
$7.70 |
Electricity Fees | $450 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $480,699 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $416,361 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $218,599 | $25,000 |
$192,927
1,105,209
kWh
|
$25,672
-
kW-mo/yr
|
|
02 | 2.7221: Lower temperature during the winter season and vice-versa | $143,524 | $2,000 |
$135,183
773,460
kWh
|
$8,341
-
kW-mo/yr
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $62,935 | $60,000 |
$59,208
338,748
kWh
|
$3,727
-
kW-mo/yr
|
|
04 | 2.7221: Lower temperature during the winter season and vice-versa | $50,254 | $2,000 |
$47,333
270,820
kWh
|
$2,921
-
kW-mo/yr
|
|
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,674 | $1,210 |
$2,366
13,540
kWh
|
$1,308
-
kW-mo/yr
|
|
06 | 2.4323: Use optimum size and capacity equipment | $1,403 | $4,531 |
$1,243
7,112
kWh
|
$160
-
kW-mo/yr
|
|
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $310 | $40 |
$234
2,117
kWh
|
$76
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $480,699 | $94,781 |
$438,494
2,511,006
kWh
|
$42,205
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $416,361 | $30,250 |
$378,043
2,165,146
kWh
|
$38,318
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs