Assessment Year | 2008 |
---|---|
Principal Product | Tempered Glass |
NAICS | 327215: Glass Product Manufacturing Made of Purchased Glass |
SIC | 3231: Glass Products, Made of Purchased Glass |
Sales Range | $10 M to 50M |
# of Employees | 238 |
Plant Area |
125,000
ft2
|
Annual Production | 25,000
thousand feet
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $889,757 | 9,572,000 |
kWh
|
$0.093 |
Electricity Demand | $120,134 | 30,041 |
kW-mo/yr
|
$4.00 |
Electricity Fees | $6,323 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $232,686 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $106,686 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 4.453: Reschedule breaks to allow for continuous production | $126,000 | $66,640 | - | - | $126,000 | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $86,926 | $83,640 |
$70,934
884,318
kWh
|
$15,992
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,860 | $8,778 |
$8,516
106,157
kWh
|
$1,344
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,695 | $1,210 |
$1,581
19,708
kWh
|
$114
-
kW-mo/yr
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $343 | $24 |
$131
1,513
kWh
|
$212
-
kW-mo/yr
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,883 | $1,210 |
$1,167
14,545
kWh
|
$3,716
-
kW-mo/yr
|
- | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,251 | $24 |
$504
6,285
kWh
|
$1,747
-
kW-mo/yr
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $728 | $1,200 |
$629
7,845
kWh
|
$99
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $232,686 | $162,726 |
$83,462
1,040,371
kWh
|
$23,224
-
kW-mo/yr
|
$126,000 | ||
TOTAL IMPLEMENTED | $106,686 | $96,086 |
$83,462
1,040,371
kWh
|
$23,224
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs