Assessment Year | 2007 |
---|---|
Principal Product | Fiberglass boats |
NAICS | 336612: Boat Building |
SIC | 3732: Boat Building and Repairing |
Sales Range | $10 M to 50M |
# of Employees | 420 |
Plant Area |
1,000,000
ft2
|
Annual Production | 2,000
pieces
|
Production Hrs. Annual | 6,600
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $511,908 | 5,747,842 |
kWh
|
$0.089 |
Electricity Demand | $61,927 | 17,950 |
kW-mo/yr
|
$3.45 |
Electricity Fees | $23,616 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $119,319 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $91,892 | $111,815 |
$85,415
1,041,645
kWh
|
$6,477
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $11,557 | $1,210 |
$8,780
107,077
kWh
|
$2,777
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,187 | $40 |
$1,004
12,242
kWh
|
$183
-
kW-mo/yr
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,330 | $1,210 |
$2,198
26,804
kWh
|
$132
-
kW-mo/yr
|
|
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,639 | $40 |
$1,482
18,073
kWh
|
$157
-
kW-mo/yr
|
|
06 | 2.4323: Use optimum size and capacity equipment | $3,802 | $3,475 |
$3,501
42,692
kWh
|
$301
-
kW-mo/yr
|
|
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,172 | $1,210 |
$2,069
25,225
kWh
|
$103
-
kW-mo/yr
|
|
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,540 | $40 |
$1,358
16,555
kWh
|
$182
-
kW-mo/yr
|
|
09 | 2.4323: Use optimum size and capacity equipment | $1,765 | $3,475 |
$1,693
20,647
kWh
|
$72
-
kW-mo/yr
|
|
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,435 | $1,210 |
$1,279
15,600
kWh
|
$156
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $119,319 | $123,725 |
$108,779
1,326,560
kWh
|
$10,540
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs