| Assessment Year | 2007 |
|---|---|
| Principal Product | Processed Fresh Produce |
| NAICS | 311991: Perishable Prepared Food Manufacturing |
| SIC | 2099: Food Preparations, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 380 |
| Plant Area |
90,000
ft2
|
| Annual Production | 100,000,000
lb
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $582,404 | 7,524,000 |
kWh
|
$0.077 |
| Electricity Demand | $45,809 | 13,305 |
kW-mo/yr
|
$3.44 |
| Electricity Fees | $93,390 | - |
|
- |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $209,293 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2628: Utilize a less expensive cooling method | $66,401 | $120,000 | - | - |
$66,401
-
MMBtu
|
|
| 02 | 2.7447: Install vinyl strip / high speed / air curtain doors | $51,399 | $22,558 |
$48,515
537,265
kWh
|
$2,884
-
kW-mo/yr
|
- | |
| 03 | 2.7447: Install vinyl strip / high speed / air curtain doors | $31,061 | $2,665 |
$29,034
362,925
kWh
|
$2,027
-
kW-mo/yr
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $16,549 | $23,640 |
$15,469
185,926
kWh
|
$1,080
-
kW-mo/yr
|
- | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,901 | $27,300 |
$14,065
155,750
kWh
|
$836
-
kW-mo/yr
|
- | |
| 06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,760 | $1,074 |
$13,679
160,925
kWh
|
$81
-
kW-mo/yr
|
- | |
| 07 | 2.2696: Use excess cold process fluid for industrial cooling needs | $7,524 | $7,800 |
$7,032
87,900
kWh
|
$492
-
kW-mo/yr
|
- | |
| 08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,179 | $30 |
$4,004
47,104
kWh
|
$175
-
kW-mo/yr
|
- | |
| 09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,909 | $180 |
$1,547
19,336
kWh
|
$362
-
kW-mo/yr
|
- | |
| 10 | 2.4323: Use optimum size and capacity equipment | $1,610 | $3,010 |
$1,514
17,816
kWh
|
$96
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $209,293 | $208,257 |
$134,859
1,574,947
kWh
|
$8,033
-
kW-mo/yr
|
$66,401
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs