Assessment Year 2004
Principal Product Sports fishing boat
NAICS 336612: Boat Building
SIC 3732: Boat Building and Repairing
Sales Range $10
M
to 50
M
# of Employees 250
Plant Area 385,000
ft2
Annual Production 70
pieces
Production Hrs. Annual 3,099
hrs
Location (State) Florida

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $156,285 3,065,500
kWh
Electricity Demand $85,231 10,925
kW-mo/yr
Electricity Fees $49,884 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $91,324 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $61,143

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Personnel Changes Savings Administrative Changes Savings
01 2.8114: Change rate schedules or other changes in utility service $13,096 $600 - - $13,096
02 2.6218: Turn off equipment when not in use $22,325 $2,300 $22,325
374,522
kWh
- -
03 2.8118: Check for accuracy of utility / power meters $15,302 $270 $15,302
167,340
kWh
- -
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $5,010 $590 $7,090
134,771
kWh
$(-2,080.0) -
05 2.4239: Eliminate or reduce compressed air usage $25,036 $50 $25,036
475,894
kWh
- -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $8,772 $25,286 $8,772
166,726
kWh
- -
07 2.4323: Use optimum size and capacity equipment $1,783 $4,328 $1,783
33,896
kWh
- -
TOTAL RECOMMENDED $91,324 $33,424 $80,308
1,353,149
kWh
$(-2,080.0) $13,096
TOTAL IMPLEMENTED $61,143 $28,226 $63,223
1,151,913
kWh
$(-2,080.0) -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Personnel Changes Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs