Assessment Year | 2003 |
---|---|
Principal Product | Al and vinyl extrusions,Stnl.steel shapes |
NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
92,622
ft2
|
Annual Production | 2,000,000
lb
|
Production Hrs. Annual | 0
hrs
|
Location (State) | Florida |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $61,320 | 1,419,630 |
kWh
|
$0.043 |
Electricity Demand | $35,165 | 4,479 |
kW-mo/yr
|
$7.85 |
Electricity Fees | $16,694 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $29,054 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,099 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,941 | $5,300 |
$1,941
35,948
kWh
|
- | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $176 | $1 |
$176
2,925
kWh
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $768 | $14 |
$768
14,222
kWh
|
- | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,001 | $270 |
$1,001
18,537
kWh
|
- | |
05 | 2.6218: Turn off equipment when not in use | $4,099 | $50 |
$4,099
75,911
kWh
|
- | |
06 | 2.4322: Use or replace with energy efficient substitutes | $2,007 | $2,630 |
$1,264
23,082
kWh
|
$743
-
kW-mo/yr
|
|
07 | 2.4322: Use or replace with energy efficient substitutes | $2,325 | $3,350 |
$1,881
34,847
kWh
|
$444
-
kW-mo/yr
|
|
08 | 2.6218: Turn off equipment when not in use | $16,737 | $60 |
$16,737
309,944
kWh
|
- | |
TOTAL RECOMMENDED | $29,054 | $11,675 |
$27,867
515,416
kWh
|
$1,187
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $4,099 | $50 |
$4,099
75,911
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs