| Assessment Year | 2001 |
|---|---|
| Principal Product | Printed music |
| NAICS |
n/a
|
| SIC | 2759: Commercial Printing, Not Elsewhere Classified |
| Sales Range | $50 M to 100M |
| # of Employees | 240 |
| Plant Area |
116,111
ft2
|
| Annual Production | 11,320,000
pieces
|
| Production Hrs. Annual | 4,420
hrs
|
| Location (State) | Florida |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $78,111 | 1,871,040 |
kWh
|
$0.042 |
| Electricity Demand | $40,852 | 4,726 |
kW-mo/yr
|
$8.64 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $50,370 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $36,730 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7111: Reduce illumination to minimum necessary levels | $4,216 | $1,000 |
$4,216
43,421
kWh
|
- | - | - | |
| 02 | 2.7111: Reduce illumination to minimum necessary levels | $7,470 | $208 |
$7,470
99,568
kWh
|
- | - | - | |
| 03 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $9,746 | $280 |
$9,746
129,842
kWh
|
- | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,029 | - |
$1,308
16,354
kWh
|
$721
-
kW-mo/yr
|
- | - | |
| 05 | 3.6192: Use a less expensive method of waste removal | $5,179 | $5,000 | - | - |
$5,179
-
gal
|
- | |
| 06 | 3.5316: Contract a wood pallet recycling company | $8,902 | $306 | - | - | - |
$8,902
-
lb
|
|
| 07 | 2.7221: Lower temperature during the winter season and vice-versa | $3,176 | $13 |
$3,176
17,090
kWh
|
- | - | - | |
| 08 | 2.7221: Lower temperature during the winter season and vice-versa | $5,511 | $13 |
$5,511
22,786
kWh
|
- | - | - | |
| 09 | 2.7232: Replace existing hvac unit with high efficiency model | $4,141 | $8,000 |
$4,141
42,653
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $50,370 | $14,820 |
$35,568
371,714
kWh
|
$721
-
kW-mo/yr
|
$5,179
-
gal
|
$8,902
-
lb
|
||
| TOTAL IMPLEMENTED | $36,730 | $6,612 |
$22,649
213,139
kWh
|
- |
$5,179
-
gal
|
$8,902
-
lb
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs