Assessment Year | 2012 |
---|---|
Principal Product | Juice Packaging |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $10 M to 50M |
# of Employees | 140 |
Plant Area |
50,000
ft2
|
Annual Production | 1,500
Tgal
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $787,961 | 9,269,935 |
kWh
|
$0.085 |
Electricity Demand | $208,842 | 20,178 |
kW-mo/yr
|
$10.35 |
Electricity Fees | $3,900 | - |
|
- |
Natural Gas | $199,320 | 25,723 |
MMBtu
|
$7.75 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $31,452 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $256 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.2611: Moderate cooling tower outlet temperature | $8,920 | $8,000 |
$8,920
104,940
kWh
|
- | |
02 | 2.4131: Size electric motors for peak operating efficiency | $8,141 | $8,000 |
$8,141
95,776
kWh
|
- | |
03 | 2.2414: Use waste heat from hot flue gases to preheat | $7,897 | $38,000 | - |
$7,897
-
MMBtu
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,230 | $20,000 |
$5,230
61,535
kWh
|
- | |
05 | 2.2511: Insulate bare equipment | $1,008 | $730 | - |
$1,008
-
MMBtu
|
|
06 | 2.2511: Insulate bare equipment | $256 | $400 | - |
$256
-
MMBtu
|
|
TOTAL RECOMMENDED | $31,452 | $75,130 |
$22,291
262,251
kWh
|
$9,161
-
MMBtu
|
||
TOTAL IMPLEMENTED | $256 | $400 | - |
$256
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs