Assessment Year | 2012 |
---|---|
Principal Product | Syntatic Foam and Tape |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 23 |
Plant Area |
80,000
ft2
|
Annual Production | 1,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $253,720 | 2,196,640 |
kWh
|
$0.12 |
Electricity Demand | $80,358 | 6,229 |
kW-mo/yr
|
$12.90 |
Natural Gas | $35,598 | 12,456 |
MMBtu
|
$2.86 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $48,798 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,311 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.8121: Apply for tax-free status for energy purchases | $19,562 | $150 | - | - | $19,562 | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,698 | $59,484 |
$12,750
110,484
kWh
|
$1,948
-
kW-mo/yr
|
- | - | |
03 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $5,802 | $22,500 |
$12,154
105,312
kWh
|
- | - |
$(-6,352.0)
-
MMBtu
|
|
04 | 2.2511: Insulate bare equipment | $4,676 | $2,250 |
$4,676
40,523
kWh
|
- | - | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,749 | - |
$1,820
15,768
kWh
|
$929
-
kW-mo/yr
|
- | - | |
06 | 2.2437: Recover waste heat from equipment | $1,070 | $1,700 | - | - | - |
$1,070
-
MMBtu
|
|
07 | 2.2511: Insulate bare equipment | $241 | $345 | - | - | - |
$241
-
MMBtu
|
|
TOTAL RECOMMENDED | $48,798 | $86,429 |
$31,400
272,087
kWh
|
$2,877
-
kW-mo/yr
|
$19,562 |
$(-5,041.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $22,311 | $150 |
$1,820
15,768
kWh
|
$929
-
kW-mo/yr
|
$19,562 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs