Assessment Year | 2023 |
---|---|
Principal Product | Hook and Loop Fasteners |
NAICS | 339993: Fastener, Button, Needle, and Pin Manufacturing |
SIC | 3965: Fasteners, Buttons, Needles, and Pins |
Sales Range | $50 M to 100M |
# of Employees | 205 |
Plant Area |
420,000
ft2
|
Annual Production | 15,000
thousand feet
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,383,331 | 15,983,143 |
kWh
|
$0.087 |
Electricity Demand | $624,551 | 73,172 |
kW-mo/yr
|
$8.54 |
Electricity Fees | $41,051 | - |
|
- |
Natural Gas | $1,074,896 | 133,474 |
MMBtu
|
$8.05 |
TOTAL YEARLY COSTS | $3,123,829 | |||
RECOMMENDED SAVINGS* | $1,275,202 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $1,034,369 | $4,078,943 |
$2,068,727
15,183,986
kWh
|
- | $(-206,873.0) |
$(-538,989.0)
-
MMBtu
|
$(-288,496.0) | |
02 | 2.9114: Use solar heat to make electricty | $166,304 | $1,812,686 |
$160,065
1,692,032
kWh
|
$6,239
-
kW-mo/yr
|
- | - | - | |
03 | 2.2437: Recover waste heat from equipment | $20,649 | $46,300 |
$9,509
100,513
kWh
|
$1,178
-
kW-mo/yr
|
- |
$9,962
-
MMBtu
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,456 | $15,900 |
$11,980
126,642
kWh
|
$1,476
-
kW-mo/yr
|
- | - | - | |
05 | 2.2437: Recover waste heat from equipment | $11,753 | $40,550 | - | - | - |
$12,443
-
MMBtu
|
$(-690.0) | |
06 | 2.2437: Recover waste heat from equipment | $28,671 | $72,000 | - | - | - |
$28,671
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $1,275,202 | $6,066,379 |
$2,250,281
17,103,173
kWh
|
$8,893
-
kW-mo/yr
|
$(-206,873.0) |
$(-487,913.0)
-
MMBtu
|
$(-289,186.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs