| Assessment Year | 2022 |
|---|---|
| Principal Product | Treated water |
| NAICS | 221310: Water Supply and Irrigation Systems |
| SIC | 4941: Water Supply |
| Sales Range | $1 M to 5M |
| # of Employees | 8 |
| Plant Area |
25,000
ft2
|
| Annual Production | 1,000,000
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $205,954 | 1,031,800 |
kWh
|
$0.20 |
| Electricity Demand | $57,973 | 2,560 |
kW-mo/yr
|
$22.65 |
| Electricity Fees | $1,536 | - |
|
- |
| Natural Gas | $8,818 | 1,508 |
MMBtu
|
$5.85 |
| TOTAL YEARLY COSTS | $274,281 | |||
| RECOMMENDED SAVINGS* | $80,298 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $27,047 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.9114: Use solar heat to make electricty | $50,962 | $247,937 |
$30,791
154,264
kWh
|
$6,251
-
kW-mo/yr
|
$13,920 | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $19,685 | $11,100 |
$19,685
98,623
kWh
|
- | - | |
| 03 | 2.7234: Use heat pump for space conditioning | $5,243 | $7,450 |
$4,541
22,750
kWh
|
$702
-
kW-mo/yr
|
- | |
| 04 | 3.1191: Change procedures / equipment / operating conditions | $2,289 | $900 |
$2,289
11,473
kWh
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,119 | $11,630 |
$1,032
5,171
kWh
|
$1,087
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $80,298 | $279,017 |
$58,338
292,281
kWh
|
$8,040
-
kW-mo/yr
|
$13,920 | ||
| TOTAL IMPLEMENTED | $27,047 | $30,180 |
$25,258
126,544
kWh
|
$1,789
-
kW-mo/yr
|
- | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs