Assessment Year | 2022 |
---|---|
Principal Product | Specialty paper |
NAICS | 322121: Paper (except Newsprint) Mills |
SIC | 2621: Paper Mills |
Sales Range | $100 M to 500M |
# of Employees | 57 |
Plant Area |
80,000
ft2
|
Annual Production | 22,782
ton
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $1,705,591 | 20,936,000 |
kWh
|
$0.081 | |
Electricity Demand | $268,202 | 33,525 |
kW-mo/yr
|
$8.00 | |
Electricity Fees | $207 | - |
|
- | |
Fuel Oil #2 | $52,871 | 3,774 |
MMBtu
|
$14.01 | |
Wood | $740,756 | 349,213 |
MMBtu
|
$2.12 | |
Waste Disposal Costs | |||||
Water Usage | $8,828 | 827 |
Tgal
|
$10.68 | |
TOTAL YEARLY COSTS | $2,776,455 | ||||
RECOMMENDED SAVINGS* | $674,814 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Wood Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 4.111: Add equipment/ operators to reduce production bottleneck | $443,207 | $3,043,367 | - | - |
$53,012
-
MMBtu
|
- | - | $390,195 | |
02 | 2.2444: Use hot process fluids to preheat incoming process fluids | $127,245 | $144,842 | - | - |
$127,245
-
MMBtu
|
- | - | - | |
03 | 2.9114: Use solar heat to make electricty | $64,198 | $280,195 |
$32,813
405,097
kWh
|
$3,984
-
kW-mo/yr
|
- | - | $27,401 | - | |
04 | 2.2437: Recover waste heat from equipment | $29,256 | $3,515 | - | - |
$35,756
-
MMBtu
|
$(-6,500.0) | - | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,386 | $12,000 |
$8,578
105,900
kWh
|
$1,808
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.2511: Insulate bare equipment | $522 | $910 | - | - |
$522
-
MMBtu
|
- | - | - | |
TOTAL RECOMMENDED | $674,814 | $3,484,829 |
$41,391
510,997
kWh
|
$5,792
-
kW-mo/yr
|
$216,535
-
MMBtu
|
$(-6,500.0) | $27,401 | $390,195 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Wood Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Product Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs