ITAC Assessment: MA0805
ITAC logo
ITAC Assessment: MA0805
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2019
Principal Product Plastic products for mediacl devices
NAICS 326199: All Other Plastics Product Manufacturing
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 780
Plant Area 190,000
ft2
Annual Production 120,000
units
Production Hrs. Annual 8,736
hrs
Location (State) Massachusetts

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $2,265,262 16,920,400
kWh
Electricity Demand $167,114 31,892
kW-mo/yr
Electricity Fees $(-6,213.0) -
Natural Gas $128,418 10,564
MMBtu
Waste Disposal Costs
Water Usage $60,031 8,972,435
Tgal
Water Disposal $45,023 8,972
Tgal
TOTAL YEARLY COSTS $2,659,635
RECOMMENDED SAVINGS* $366,656 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $112,694

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Water Disposal Savings One-time Revenue or Avoided Cost Savings
01 2.7241: Install outside air damper / economizer on hvac unit $96,513 $144,000 $96,513
720,244
kWh
- - -
02 2.7142: Utilize higher efficiency lamps and/or ballasts $82,405 $128,486 $77,380
577,463
kWh
$5,025
-
kW-mo/yr
- -
03 2.9113: Use solar heat for heat $77,280 $383,955 $62,315
465,041
kWh
- - $14,965
04 2.2614: Use cooling tower or economizer to replace chiller cooling $40,486 $165,914 $40,486
302,135
kWh
- - -
05 2.7232: Replace existing hvac unit with high efficiency model $28,514 $32,800 $28,514
212,792
kWh
- - -
06 3.4116: Meter recycled water (to reduce sewer charges) $25,552 $7,916 - - $25,552
-
Tgal
-
07 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $14,131 $5,222 $14,131
105,458
kWh
- - -
08 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $1,775 $200 $1,775
13,247
kWh
- - -
TOTAL RECOMMENDED $366,656 $868,493 $321,114
2,396,380
kWh
$5,025
-
kW-mo/yr
$25,552
-
Tgal
$14,965
TOTAL IMPLEMENTED $112,694 $161,486 $107,669
803,502
kWh
$5,025
-
kW-mo/yr
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Water Disposal Savings One-time Revenue or Avoided Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs