Assessment Year | 2018 |
---|---|
Principal Product | Medical equipment |
NAICS | 334418: Printed Circuit Assembly (Electronic Assembly) Manufacturing |
SIC | 3845: Electromedical and Electrotherapeutic Apparatus |
Sales Range | $100 M to 500M |
# of Employees | 700 |
Plant Area |
513,000
ft2
|
Annual Production | 270,000
units
|
Production Hrs. Annual | 6,268
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,602,854 | 15,280,440 |
kWh
|
$0.10 |
Electricity Demand | $539,264 | 33,216 |
kW-mo/yr
|
$16.24 |
Electricity Fees | $(-57,762.0) | - |
|
- |
Natural Gas | $53,840 | 10,702 |
MMBtu
|
$5.03 |
TOTAL YEARLY COSTS | $2,138,196 | |||
RECOMMENDED SAVINGS* | $54,147 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,594 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $34,323 | $28,940 |
$34,323
326,884
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,582 | $5,974 |
$6,634
63,181
kWh
|
$1,948
-
kW-mo/yr
|
- | |
03 | 2.7221: Lower temperature during the winter season and vice-versa | $8,289 | $5,525 |
$6,675
63,569
kWh
|
- |
$1,614
-
MMBtu
|
|
04 | 2.6218: Turn off equipment when not in use | $1,522 | $1,000 |
$1,522
14,492
kWh
|
- | - | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,012 | $500 |
$1,012
9,634
kWh
|
- | - | |
06 | 2.7314: Reduce ventilation air | $419 | $1,000 |
$39
371
kWh
|
- |
$380
-
MMBtu
|
|
TOTAL RECOMMENDED | $54,147 | $42,939 |
$50,205
478,131
kWh
|
$1,948
-
kW-mo/yr
|
$1,994
-
MMBtu
|
||
TOTAL IMPLEMENTED | $9,594 | $6,474 |
$7,646
72,815
kWh
|
$1,948
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs