Assessment Year | 2017 |
---|---|
Principal Product | Waste water treatment |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | $10 M to 50M |
# of Employees | 43 |
Plant Area |
100,000
ft2
|
Annual Production | 6,205,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,034,023 | 11,995,247 |
kWh
|
$0.086 |
Electricity Demand | $316,099 | 24,352 |
kW-mo/yr
|
$12.98 |
Electricity Fees | $7,690 | - |
|
- |
TOTAL YEARLY COSTS | $1,357,812 | |||
RECOMMENDED SAVINGS* | $164,904 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $85,936 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4131: Size electric motors for peak operating efficiency | $64,908 | $71,450 |
$64,908
754,740
kWh
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $35,884 | $24,000 |
$35,884
417,259
kWh
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $26,360 | $16,650 |
$26,360
306,514
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,530 | $41,013 |
$12,025
139,823
kWh
|
$2,505
-
kW-mo/yr
|
|
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,498 | $18,391 |
$5,097
59,271
kWh
|
$1,401
-
kW-mo/yr
|
|
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,233 | $16,685 |
$14,233
165,495
kWh
|
- | |
07 | 3.1191: Change procedures / equipment / operating conditions | $2,491 | $500 |
$2,491
28,963
kWh
|
- | |
TOTAL RECOMMENDED | $164,904 | $188,689 |
$160,998
1,872,065
kWh
|
$3,906
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $85,936 | $130,854 |
$82,030
953,834
kWh
|
$3,906
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs