| Assessment Year | 2017 |
|---|---|
| Principal Product | metal nozzles |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 130 |
| Plant Area |
60,000
ft2
|
| Annual Production | 24,000,000
pieces
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $179,440 | 1,452,733 |
kWh
|
$0.12 |
| Electricity Demand | $60,299 | 4,577 |
kW-mo/yr
|
$13.17 |
| Electricity Fees | $8,766 | - |
|
- |
| LPG | $103,573 | 7,028 |
MMBtu
|
$14.74 |
| TOTAL YEARLY COSTS | $352,078 | |||
| RECOMMENDED SAVINGS* | $34,391 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $15,673 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | LPG Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $16,653 | $30,000 | - |
$16,653
-
MMBtu
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,580 | $14,050 |
$8,580
69,196
kWh
|
- | |
| 03 | 2.7313: Recycle air for heating, ventilation and air conditioning | $5,593 | $10,625 |
$(-6,167.0)
(-49,761)
kWh
|
$11,760
-
MMBtu
|
|
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,564 | $6,660 |
$1,564
12,611
kWh
|
- | |
| 05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,500 | $1,000 |
$1,500
12,098
kWh
|
- | |
| 06 | 2.1122: Re-size charging openings or add a movable door on equipment | $501 | $100 | - |
$501
-
MMBtu
|
|
| TOTAL RECOMMENDED | $34,391 | $62,435 |
$5,477
44,144
kWh
|
$28,914
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $15,673 | $25,675 |
$3,913
31,533
kWh
|
$11,760
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | LPG Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs