Assessment Year 2008
Principal Product Thermoformed Plastic Packaging
NAICS 561910: Packaging and Labeling Services
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 75
Plant Area 63,000
ft2
Annual Production 50,000,000
pieces
Production Hrs. Annual 6,864
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $150,987 2,436,000
kWh
Electricity Demand $56,772 6,528
kW-mo/yr
Electricity Fees $(-14,276.0) -
LPG $22,120 67
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $107,252 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $31,658

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.6218: Turn off equipment when not in use $19,525 - $19,525
275,000
kWh
-
02 2.4224: Upgrade controls on compressors $9,089 $10,000 $9,089
128,014
kWh
-
03 2.4221: Install compressor air intakes in coolest locations $1,807 $160 $1,807
25,454
kWh
-
04 2.2511: Insulate bare equipment $1,472 $268 $1,472
20,720
kWh
-
05 2.7135: Install occupancy sensors $165 $127 $165
2,328
kWh
-
06 2.7142: Utilize higher efficiency lamps and/or ballasts $11,968 $36,000 $11,756
165,580
kWh
$212
-
kW-mo/yr
07 2.9114: Use solar heat to make electricty $63,226 $1,600,000 $63,226
285,000
kWh
-
TOTAL RECOMMENDED $107,252 $1,646,555 $107,040
902,096
kWh
$212
-
kW-mo/yr
TOTAL IMPLEMENTED $31,658 $36,127 $31,446
442,908
kWh
$212
-
kW-mo/yr
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs