Assessment Year | 2015 |
---|---|
Principal Product | Fabricated metal parts |
NAICS | 332322: Sheet Metal Work Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 67 |
Plant Area |
18,000
ft2
|
Annual Production | 1,700,000
lb
|
Production Hrs. Annual | 4,394
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $62,114 | 585,987 |
kWh
|
$0.11 |
Electricity Demand | $30,434 | 2,167 |
kW-mo/yr
|
$14.04 |
Electricity Fees | $388 | - |
|
- |
Fuel Oil #2 | $20,205 | 764 |
MMBtu
|
$26.45 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $6,155 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,455 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,700 | $3,600 |
$3,700
34,903
kWh
|
|
02 | 2.7135: Install occupancy sensors | $1,433 | $1,224 |
$1,433
13,518
kWh
|
|
03 | 2.7232: Replace existing hvac unit with high efficiency model | $1,022 | $36,150 |
$1,022
9,642
kWh
|
|
TOTAL RECOMMENDED | $6,155 | $40,974 |
$6,155
58,063
kWh
|
||
TOTAL IMPLEMENTED | $2,455 | $37,374 |
$2,455
23,160
kWh
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs