Assessment Year | 2011 |
---|---|
Principal Product | Extruded plastic |
NAICS | 325991: Custom Compounding of Purchased Resins |
SIC | 3087: Custom Compounding of Purchased Plastics Resins |
Sales Range | $10 M to 50M |
# of Employees | 67 |
Plant Area |
44,000
ft2
|
Annual Production | 325
ton
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $193,738 | 1,578,960 |
kWh
|
$0.12 |
Electricity Demand | $49,371 | 3,974 |
kW-mo/yr
|
$12.42 |
Electricity Fees | $4,800 | - |
|
- |
Natural Gas | $37,540 | 2,931 |
MMBtu
|
$12.81 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $9,539 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,325 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7314: Reduce ventilation air | $6,162 | $9,261 |
$4,709
38,384
kWh
|
$1,453
-
MMBtu
|
|
02 | 2.4237: Substitute compressed air cooling with water or air cooling | $1,294 | $1,220 |
$1,294
10,548
kWh
|
- | |
03 | 2.7135: Install occupancy sensors | $1,163 | $1,265 |
$1,163
9,480
kWh
|
- | |
04 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $768 | $300 |
$768
6,262
kWh
|
- | |
05 | 2.2511: Insulate bare equipment | $152 | $80 |
$152
1,236
kWh
|
- | |
TOTAL RECOMMENDED | $9,539 | $12,126 |
$8,086
65,910
kWh
|
$1,453
-
MMBtu
|
||
TOTAL IMPLEMENTED | $7,325 | $10,526 |
$5,872
47,864
kWh
|
$1,453
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs