Assessment Year | 2011 |
---|---|
Principal Product | Steel Investment castings |
NAICS | 331512: Steel Investment Foundries |
SIC | 3324: Steel Investment Foundries |
Sales Range | $10 M to 50M |
# of Employees | 165 |
Plant Area |
110,000
ft2
|
Annual Production | 15,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $972,900 | 9,002,755 |
kWh
|
$0.11 |
Electricity Demand | $177,973 | 22,560 |
kW-mo/yr
|
$7.89 |
Electricity Fees | $960 | - |
|
- |
Natural Gas | $339,899 | 35,505 |
MMBtu
|
$9.57 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $77,768 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $65,116 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $27,383 | $88,700 |
$27,383
270,045
kWh
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $21,204 | $5,760 |
$21,204
209,118
kWh
|
|
03 | 2.6218: Turn off equipment when not in use | $9,343 | - |
$9,343
92,144
kWh
|
|
04 | 2.6218: Turn off equipment when not in use | $7,186 | - |
$7,186
70,873
kWh
|
|
05 | 2.2622: Replace existing chiller with high efficiency model | $6,819 | $26,495 |
$6,819
67,249
kWh
|
|
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,833 | $8,590 |
$5,833
57,520
kWh
|
|
TOTAL RECOMMENDED | $77,768 | $129,545 |
$77,768
766,949
kWh
|
||
TOTAL IMPLEMENTED | $65,116 | $94,460 |
$65,116
642,180
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs