Assessment Year | 2009 |
---|---|
Principal Product | Optical components and assemblies |
NAICS | 333314: Optical Instrument and Lens Manufacturing |
SIC | 3827: Optical Instruments and Lenses |
Sales Range | $10 M to 50M |
# of Employees | 146 |
Plant Area |
100,000
ft2
|
Annual Production | 728,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $506,130 | 3,794,682 |
kWh
|
$0.13 |
Electricity Demand | $51,671 | 7,406 |
kW-mo/yr
|
$6.98 |
Electricity Fees | $20,682 | - |
|
- |
Natural Gas | $7,812 | 303 |
MMBtu
|
$25.78 |
LPG | $184,573 | 7,544 |
MMBtu
|
$24.47 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $32,506 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,132 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | LPG Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7311: Ventilation system to shut off when room is not in use | $11,122 | $1,990 |
$495
3,614
kWh
|
- | - |
$10,627
-
MMBtu
|
|
02 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $10,132 | $23,474 |
$10,132
73,953
kWh
|
- | - | - | |
03 | 2.6218: Turn off equipment when not in use | $7,667 | - |
$5,927
43,264
kWh
|
$1,740
-
kW-mo/yr
|
- | - | |
04 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $3,585 | $6,600 |
$1,900
13,866
kWh
|
- |
$1,685
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $32,506 | $32,064 |
$18,454
134,697
kWh
|
$1,740
-
kW-mo/yr
|
$1,685
-
MMBtu
|
$10,627
-
MMBtu
|
||
TOTAL IMPLEMENTED | $10,132 | $23,474 |
$10,132
73,953
kWh
|
- | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs