| Assessment Year | 2006 |
|---|---|
| Principal Product | Hot stam foil |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3497: Metal Foil and Leaf |
| Sales Range | $10 M to 50M |
| # of Employees | 75 |
| Plant Area |
60,000
ft2
|
| Annual Production | 937,500
thousand feet
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $417,519 | 4,778,250 |
kWh
|
$0.087 |
| Electricity Demand | $56,108 | 10,889 |
kW-mo/yr
|
$5.15 |
| Electricity Fees | $847 | - |
|
- |
| Natural Gas | $148,427 | 13,429 |
MMBtu
|
$11.05 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $53,400 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $24,092 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | By-product Production Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $25,107 | $85,300 |
$25,107
273,500
kWh
|
- | - | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $9,984 | $17,660 |
$8,555
93,200
kWh
|
$1,429
-
kW-mo/yr
|
- | - | |
| 03 | 2.2511: Insulate bare equipment | $5,643 | $17,818 | - | - |
$5,643
-
MMBtu
|
- | |
| 04 | 2.7314: Reduce ventilation air | $4,902 | $1,000 | - | - |
$4,902
-
MMBtu
|
- | |
| 05 | 4.113: Install refrigeration system to cool product | $3,292 | $19,000 |
$(-83.0)
(-900)
kWh
|
- | - | $3,375 | |
| 06 | 2.2511: Insulate bare equipment | $2,161 | $668 | - | - |
$2,161
-
MMBtu
|
- | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,402 | - |
$1,202
13,100
kWh
|
$200
-
kW-mo/yr
|
- | - | |
| 08 | 2.7135: Install occupancy sensors | $909 | $775 |
$909
9,900
kWh
|
- | - | - | |
| TOTAL RECOMMENDED | $53,400 | $142,221 |
$35,690
388,800
kWh
|
$1,629
-
kW-mo/yr
|
$12,706
-
MMBtu
|
$3,375 | ||
| TOTAL IMPLEMENTED | $24,092 | $37,146 |
$9,757
106,300
kWh
|
$1,629
-
kW-mo/yr
|
$12,706
-
MMBtu
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | By-product Production Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs